              Conventonal Network LCD 2-Wire 4-Zone Fire Alarm Kit
              • Conventonal Network LCD 2-Wire 4-Zone Fire Alarm KitConventonal Network LCD 2-Wire 4-Zone Fire Alarm Kit
              • Conventonal Network LCD 2-Wire 4-Zone Fire Alarm KitConventonal Network LCD 2-Wire 4-Zone Fire Alarm Kit
              • Conventonal Network LCD 2-Wire 4-Zone Fire Alarm KitConventonal Network LCD 2-Wire 4-Zone Fire Alarm Kit
              • Conventonal Network LCD 2-Wire 4-Zone Fire Alarm KitConventonal Network LCD 2-Wire 4-Zone Fire Alarm Kit

              Conventonal Network LCD 2-Wire 4-Zone Fire Alarm Kit

              Conventonal Network LCD 2-Wire 4-Zone Fire Alarm KitIntroduction:1 AW-CFP2166 series conventional fire alarm panel is designed based on EN54 part 2&4 standard.2 It is modularized design, the panel can expend from 1 zone to 32 zones easily.3 It has 2 level control mode by a lock4 It has 24VDC and......

              Send Inquiry

              Product Description

              Conventonal Network LCD 2-Wire 4-Zone Fire Alarm Kit

              Conventonal Network LCD 2-Wire 4-Zone Fire Alarm Kit
              Conventonal Network LCD 2-Wire 4-Zone Fire Alarm Kit


              Introduction:

              1 AW-CFP2166 series conventional fire alarm panel is designed based on EN54 part 2&4 standard.
              2 It is modularized design, the panel can expend from 1 zone to 32 zones easily.
              3 It has 2 level control mode by a lock
              4 It has 24VDC and 5VDC power supply output.
              5 It has FIRE and FAULT signal output.
              6 It has 2 general sounders output.
              7 Each zone has 1 circuit detectors input.
              8 Each zone can be disable by a button.
              9 It has RESET button to reset the panel.
              10 It has SILENCE button to stop BUZZER and SOUNDERS.
              11 It has EVACUATE button to start a manual fire alarm immediately.
              12 It has battery low protection function, when battery voltage lower than 21VDC, battery will be cut off automatically until the mains power is on.
              13 It has an optional GSM module for fire alarm by SMS.
              14 It is economic, user-friendly and easy maintenance.

              Parameters:
              ITEM1Zone panel2Zone panel4-8 Zone panel12-32 Zone panel
              Model No.AW-CFP2166-01AW-CFP2166-02AW-CFP2166-04-8AW-CFP2166-12-32
              Power specification
               
              Mains supply voltage110VAC or 240VAC
              Internal power supply27.2VDC
              Total output current limited500mA @ 240VAC500mA @ 240VAC3A @ 240VAC3A @ 240VAC
              Main supply monitor for faultYes
              Battery protection for low voltageYes
              Batteries (default configuration)12V2AH*2
              Detector circuit specification
               
              Number of circuit124-164-32
              Line fault monitor for open circuitYes
              Line fault monitor for short circuitYes
              Line fault monitor for detector removalYes, if End of Line Monitor Unit fitted in place of End of Line Resistor
              End of Line device6.8k Ω,5% tolerance, 0.25W (colour code-blue,grey,red,gold)
              Detector continuity diodesSilicon 1N4001 or Schottky type (required if End of Line Monitor Unit fitted to give Detector Removal Fault)
              Call point resistor value470 to 680 Ω, 0.225 or 0.5 watt
              Maximum number of smoke/heat detectors per zone20 (based on a total detector current of 2mA, each detector consuming 100μA).Note: if End of Line Monitor Unit is fitted, for correct operation maxmum voltage drop must not exceed 12 volts.
              Maximum number of manual call points per zoneNo limit
              Sounder circuit specification
               
              Number of general circuits2
              End of line resistor value6.8k Ω,5% tolerance, 0.25W (colour code-blue,grey,red,gold)
              Line fault monitor for open circuitYes
              Line fault monitor for short circuitYes
              Outputs fused AT400mA
              Maximum number of bells @ 20mA of each sounder output20
              Fuses
               
              Battery fuse1.5A F 20mm
              Sounder outputs500mA F 20mm
              Fire and fault output
               
              Output typeNC and NO relay
              Maximum current100mA
              Connection block
               
              Largest acceptable conductor size2.5mm2
              Smallest acceptable conductor size0.75mm2
              Size and weight
               

               
              Dimensions(mm)272*200*70mm320*231*90mm395X502X124362X565X124
              Weight (without batteries)4kg5kg7kg8kg
              Weight (with batteries)5.8kg6.8kg9.6kg12.5kg