Application:Water mist nozzles apply to extinguishing the hazardous solid surface fire in relatively confined space, combustible liquid fire and part of energized equipment fire. Mainly used in libraries, archives, high-rise buildings, production workshop, cable tunnel, oil immersed transformer, boi......

Application:
Water mist nozzles apply to extinguishing the hazardous solid surface fire in relatively confined space, combustible liquid fire and part of energized equipment fire. Mainly used in libraries, archives, high-rise buildings, production workshop, cable tunnel, oil immersed transformer, boiler room, electronic information system room, generator room and other places.
Performance data:
Model Code | K factor | Working | Flow rate(L/min) | Max. Distance between nozzles | Max fit height | Qty of Nozzles tips |
CY--T1.0/10-57ºC2 | 1.0 | 10-14Mpa | 10-11.8 | 3m | 5m | 5/6/7 |
CY--T1.5/10-57ºC2 | 1.5 | 10-14Mpa | 12-14.2 | 3m | 5m | 5/6/7 |
CY--T1.7/10-57ºC2 | 1.7 | 10-14Mpa | 15-17.7 | 3m | 5m | 5/6/7 |
CY--T2.0/10-57ºC2 | 2.0 | 10-14Mpa | 17-20.1 | 3m | 5m | 5/6/7 |
CY--T2.5/10-57ºC2 | 2.5 | 10-14Mpa | 20-23.7 | 3m | 5m | 5/6/7 |
CY--T1.0/10-57ºC2 | 1.0 | 5.0-10Mpa | 12.5-29.6 | 3m | 5m | 5/6/7 |
Operating Temperature/Colour | Brand | Model Code | Diameter | RTI[sqrt(ms)] |
57ºC2/Orange 68ºC/Red | JOB | F2/S2 | 2 | 19 |
57ºC/Orange 68ºC/Red | JOB | F2.5 | 2.5 | 24 |








Fire Fighting Equipment of UL Listed Fire Sprinkler
Fire Fighting Equipment of Fire Sprinkler with UL Approval
Fire Fighting Equipment of Dn20 Sidewall Fire Sprinkler
UL, SGS, CCS, Cccf, BV Fire Water Monitor for Fire Fighting System, 1.2MPa
Fast Response Fire Sprinkler, Fire Fighting , Sprinkler System, Fire Sprinkler Head